Facilities Management UC Davis Link Facilities Management Link
Buildings & Grounds / Building Maintenance / Renovation & Construction / Utilities / Resource Management / Information Systems & Human Resources

or report a problem via
phone . . . 752-1655
or email . . .

Web Work Request Info
Sewer Disposal Guidelines

UC Davis Local Limits

The documents in the Sewer Disposal Guidelines Menu (to the left) present policies and procedures regarding discharges to the UC Davis sanitary sewer system. Questions or inquiries regarding sewer disposal should be directed to at (530) 754-5819 or to at (530) 754-8214.

IMPORTANT!


Currently, the constituents of greatest concern for the campus are salts (measured as total dissolved solids or electrical conductivity), copper, aluminum, and cyanide. The wastewater treatment plant has historically experienced permit violations for these three pollutants. Accordingly, the campus community is urged to be especially vigilant in following sewer disposal policies for these constituents. The following sewer discharge limits are in place:

  • Electrical Conductivity: Wastewater shall not cause or contribute to permit violations at the wastewater treatment plant. Any sewer discharges that exceed 900 umhos/cm and any new proposed water softeners (or other water treatment devices that discharge waste brine) must be approved by at (530) 754-8214.
  • Aluminum: Watewater shall not contain greater than 87 parts per billion.
  • Copper: No added copper allowed.
  • Cyanide: Wastewater shall not contain greater than 20 parts per billion.

If your waste exceeds any of these limits, please contact Environmental Health and Safety (EH&S), for proper disposal at (530) 752-1493.


Facilities Management Home | ARM Home | UC Davis Home | Submit a Work Request |
© 2009 UCD Facilities Management. All rights reserved.
Please direct any comments to the
This page was last modified Tuesday April 10, 2007